Permit: T00CM05412

Parcel: 110082170

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/05/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
05/29/2001 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/ 1) REVISE DETAIL 7/2 2) SHOWER VALVE MUST BE TEMPERATURE AND PRESSURE BALANCED ANTI SCALD 3) OK TO INSULATE AND DRY WALL ALL BUT SHOWER VALVE
04/04/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. SIMPSON ST 12'S NOT INSTALLED SEE 7/2. 2. BRACES NOT INSTALLED SEE 7/2 3 PLACES. 3. PLAN CALLS FOR 24" OVERHANGS-30" EXISTS. REUSE PLAN. 4. NO CITY OF TUCSON APPROVED TRUSS DRAWINGS ON SITE. 5. BOTTOM CHORDS OF TRUSSES APPEAR TO HAVE BEEN CUT OFF AT SITE. IF THEY HAVE PROVIDE TRUSS ENGINEER EVALUATION AND OR REPAIR DOCUMENTS. 6. PROVIDE COLLAR TIES ON RAFTERS IN OVER BUILT AREA PER UBC 2326. 12.6. 7. THERE IS NO STRUCTURAL CONNECTION BETWEEN ROOF SHEATHING AND NORTH OVER HANG. HAVE ARCHITECT OF RECORD PROVIDE A CITY APPROVED DETAIL OF CONNECTION.