Permit: T00CM05401

Parcel: 110060550

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/29/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*NOTE TO CONTR. THE USE OF CAULKING TO SUPPORT CABLE AT THE MULTI GANG BOXES IS NOT PER LISTING OF THE BOX MANUFACTURER AS A CABLE CLAMP. THIS TIME I WILL LET IT GO, BUT DON'T DO IT AGAIN. THANKS FOR STAPLING CABLE CLOSE TO THE BOXES. PLEASE READ ART 370-17. NEC 99 I HOPE THIS WILL CLEAR IT UP FOR YOU. NEED TO SEE REVISED PLANS PRIOR TO FINAL PER LAST 2 INSP. WRITE UPS.
04/25/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTES 1.) PROVIDE LISTING OF LARGE ROMEX CONNECTOR WITH MULTI CABLES CLAMPED AT INSIDE PANEL APPROVING USE AS SUCH, OTHER WISE CLAMP CABLES WITH LISTED CONNECTORS. 110-3 NEC 110-12 90-4. 2.) SUPPORT ROMEX ABOVE PANELS PER NEC 336. WITHIN 12" OF ENCLOSURE. 3.) MULTI GANG BOXES WITH CLAMP TABS BROKEN OUT OR BENT SO AS TO CLAMP CABLE NOT APPROVED. 370-17 NEC. 4.) REVISE DRAWINGS AS PER INSP. WRITE UP 3-17-02.