Permit: T00CM05400

Parcel: 11008305F


Addresses:

2485 N SWAN RD #161


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05400

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/14/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/12/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000* 1) EX FANS NOT MADE UP.
2) HP-1 MISSING FUSES 3) 400A PANEL SHOULD BE MARKED BA BUT MARKED BB ( SWITCH LABELS)
4) PANEL SCHEDULE SWITCHED SEE PLANS
5) UNIT IN WALK-IN NEEDS SWITCH NEED TO POST BOND FOR POWER RELEASE