Permit: T00CM05400

Parcel: 11008305F


Addresses:

2485 N SWAN RD #161

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/16/2001 ELECTRIC - ABOVE CEILING Approved
01/30/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
NOTES FRONT SEATING AREA ONLY
01/26/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
MC CABEL TO CEILING J-BOX MUST BE SUPPORTED WITHIN 12" EACH BOX
334-10 NEC
SUPPORT EMT CONDUIT WITHIN 3' EACH BOX 348-13 NEC
01/05/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*