Permit: T00CM05396

Parcel: 140250190

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/31/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1)ALL CORRECTIONS MADE OK.2)CLOSET FLANGES OK.3)TUBS OK.4)OK TO COVER WALLS.
05/29/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1)ABS DWV PIPING WATER TESTED RISERS ONLY ON ROUGH/SOIL-PLUMBER IN,TRAP ARMS,CLEANOUTS,STAND PIPES FOR CLOTHES WASHERS, COUPLINGS, AND STAB OUTS FOR LAVATORIES.NEED TO SEE WATER TEST TO 42".2)TRAP ARM MAY NOT CHANGE SIZE.3)707.6 94 UPC CLEAN-OUTS TO BE INSTALLED OR VERTICAL PIPING-NOT IN THE MIDDLE OF A TRAP ARM.