Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2000 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 11/17/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1. YARD WATER LINE MUST BE CONNECTED TO METER. 2. P.E.X. TO COPPER CONNECTION ON YARD WATER COVERED WITHOUT APPROVAL--EXPOSE. 3. NO WATER TEST OF ROUGH PLUMBING PRESENTLY ONLY APPROXIMATELY 10" OF WATER COLUMN MUST BE TESTED WITH A MINIMUM FO 42" OF WATER COLUMN ABOVE FINISHED FLOOR. CHECK FOR LEAK |