Permit: T00CM05374

Parcel: 13003019B


Addresses:

2620 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/16/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
04/10/2001 MECHANICAL - FINAL Denied 1) NEED TO SECURE COOKING APPLIANCES USING THIS TYPE OF FLEX LINES FOR MOVEMENT, USE RATED FLEX GAS CONNECTORS. 2) NEED GREASE COLLECTION RECEPTICLES ON HOOD GUTTER AND EXHAUST BLOWER. 3) CONDENSORS ON ROOF, INSTALL ON PLATFORMS BASES OR 4X4 REO/WD RUNNERS, SECURE UNITS TO SAME 4) DISCHARGE TO GAS VALVE -SECURE TO STABILIZE ON UNISTRUT CLAMPS