Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* WASTE AND VENT SYSTEM OK WATER DISTRIBUTION OK ALL CORRECTIONS HAVE BEEN MADE |
|
| 01/08/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* SEE NOTE #4 AS REQUESTED MUST USE SPECIALTY COUPLING AT WEST SIDE KITCHEN SINK |
|
| 12/30/2000 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* SOIL WATER TEST BLDG SEWER OK OK TO BACKFILL BLDG SEWER AND YARD WATER LINE MUST SEE FINAL CONNECTION TO HCS AND WATER SERVICE AT METER AND BLDG MUST SECURE P&T DRAINS IN WALL |
|
| 12/26/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
| 12/22/2000 | PLUMBING - INTERMEDIATE | Not ready for Inspection | MUST USE APPROVED MATER IAL FOR P&T DRAINS HORIZONTAL VENT FOR KITCHEN SINKS MUST BE AT 42" A.F.F. MUST INSTALL CLOSET RINGS MUST USE DIRECTIONAL FITTING WHEN EXTENDING C.O. AT KI. SINK RE TEST SYSTEM |