Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T00CM05302
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
01/26/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/1. EXERCISE FUSES IN A/C CONDENSER. 35A INSTALLED 30A REQUIRED. 2. ELECTRIC OUTLETS RT OF K. SINK NOT GFCI. 3. YOU MUST PROVIDE LADDER ACCESS TO ATTIC FURNACE. IT APPEARS THAT GAS S.O.V. MAY BE MISSING. 4. BACK YARD GRADING NOT COMPLETE. |