Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/29/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000*/AT FRAMING INSPECTION SHEAR TRANSFERS TO BE COMPLETE. |
| 01/25/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/1. PROVIDE 1/8" GAP FOR AS IS ROOF SHEATHIN BLOCK UNDER BROKEN PANEL EDGES NAIL DOWN ALL SHINERS. 2. SECURE DBL TOP PLATE AT ENTRYWAY GARAGE CONNECTION. 3. H 2.5 REQUIRED AT ALL TRUSSES INCLUDING JACKS. 4. MAS AT GARAGE NOT INSTALLED PROPER 5. COMPLETE DETAIL 3/SD3 AND 9/SD3. POST TO BEAMS STRUCTUAL CONNECTIONS NOT COMPLETE AT FLOOR TRUSSES. OK TO APPLY STUCCO MESH EXCEPT AT FRONT GARAGE WALL. |
| 01/19/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. PROVIDE CS 16 X 24 STRAPS AT S.W. WALL AT SECOND FLOOR. 2. PROVIDE 6" O.C. NAILING AT SECOND FLOOR DECK. 3. PROVIDE 1/8" GAP AT EXT. SHEATHIN. 4. PROVIDE 6" O.C. NAILS AT SECOND FLOOR AT BOTTOM PLATE AT SHEARWALLS. |