Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/19/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 12/15/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1. KITCHEN VTR CANNOT RUN HORIZONTAL UNTIL 6' ABOVE FLOOD RIM OF FIXTURE SERVED. 2. PROTECT ELEC. ROMEX WITHIN 1/4 FROM EDGE OF STUD SECURE TO CENTER OF 2X. 3. PROVIDE DETAIL 6/SD2 UNDER OVER FRAME. 4. SECURE TYPE B1 VENT AT FURNACE FROM SEPERATION AT 45 DEGREE. 5. PROTECT CONDENSATE LINE AT OVER KNOTCHED DBL TOP PLATE 16 GA STRAP MINIMUM 3 16D'S |