Permit: T00CM05292

Parcel: 137338180

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/19/2000 FRAMING Approved IVRS - Inspection 0000*
12/15/2000 FRAMING Partial Approval IVRS - Inspection 0000*/1. KITCHEN VTR CANNOT RUN HORIZONTAL UNTIL 6' ABOVE FLOOD RIM OF FIXTURE SERVED. 2. PROTECT ELEC. ROMEX WITHIN 1/4 FROM EDGE OF STUD SECURE TO CENTER OF 2X. 3. PROVIDE DETAIL 6/SD2 UNDER OVER FRAME. 4. SECURE TYPE B1 VENT AT FURNACE FROM SEPERATION AT 45 DEGREE. 5. PROTECT CONDENSATE LINE AT OVER KNOTCHED DBL TOP PLATE 16 GA STRAP MINIMUM 3 16D'S