Inspection History Details
Permit: T00CM05290
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 06/12/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1. LOOSE FITTING CONDUIT UNDER PANEL 2. ROMES IN CONDUIT SYSTEM 3. LIGHT TO MEET CITY LIGHTING ORDANANCE FOR SHEILDING. 4. CLEAN SURFACE UNDER LUG. 5. CANNOT USE SHEET METAL SCREWS. | |
| 05/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935* 1) CLEAN SURFACE UNDER GROUND LUG 250-12 2) CAN NOT USE SHEET METAL SCREW 250-8 3) LOOSE SEAL TITE FITTINGS 4) STRAP AND SUPPORT SEAL TITE AS PER CODE 351-8 5) WORKING CLEARANCE IN FRONT OF POWER CABINET-NEED EVEN WORKING PLATFORM IN FRONT OF PANEL 110-26 6) LOOSE FITTINGS AT PULL GUTTER ON ROOF 7) NO WORK PROGRESS-THESE ARE ALL FROM PREVIOUS INSP A REFEE HAS BEEN ISSUED |
|
| 04/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* ELEC. SERVICE NOT FOUND. EQUIPMENT GATE LOCKED | |
| 03/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935* NO WORK PROGRESS A REFEE HAS BEEN ISSUED | |
| 03/05/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) CLEAN SURFACE BEHIND GROUND LUG SEC 250-12 2) HAS NOT BEEN CORRECTED AND IS TYPE OF SCREW USED FOR THUADED ENTRY. (CRICKET DISCONNECT SW) BY TELCO CABINET SINCE THERE WERE NO PLANS ON SITE, COULD NOT TELL WHERE GUTTER WAS OR HOW TO GET TO IT. ALSO SINCE THERE ARE TWO SERVICES ON THIS BLDG IN CLOSE PROXIMITY TO EACH OTHER, THE 1999 NEC REQUIRES THEIR GROUNDING SYSTEM TO BE TOGETHER. SEC 250-58 A COMMON GROUNDING ELECTRODE SYSTEM | |
| 02/06/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) WORKING CLEARANCES IN FRONT OF DISCONNECT. 2) CLEAN SURFACE BEHIND GROUND LUG 250-12 3) CANNOT USE SHEET METAL SCREWS 250-8 4) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD 5) LOOSE FITTINGS AT PULL GUTTER 6) NEED PERMANENT ADDRESS LABELS (NO INK) 7) NEED TO SEE AFTER CROSS OVER OK TO CLEAR POWER |