Permit: T00CM05290


Addresses:

25 E DRACHMAN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/14/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/12/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. LOOSE FITTING CONDUIT UNDER PANEL 2. ROMES IN CONDUIT SYSTEM 3. LIGHT TO MEET CITY LIGHTING ORDANANCE FOR SHEILDING. 4. CLEAN SURFACE UNDER LUG. 5. CANNOT USE SHEET METAL SCREWS.
05/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935* 1) CLEAN SURFACE UNDER GROUND LUG 250-12 2) CAN NOT USE SHEET METAL SCREW 250-8 3) LOOSE SEAL TITE FITTINGS
4) STRAP AND SUPPORT SEAL TITE AS PER CODE 351-8 5) WORKING CLEARANCE IN FRONT OF POWER CABINET-NEED EVEN WORKING PLATFORM IN FRONT OF PANEL 110-26 6) LOOSE FITTINGS AT PULL GUTTER ON ROOF 7) NO WORK PROGRESS-THESE ARE ALL FROM PREVIOUS INSP A REFEE HAS BEEN ISSUED
04/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920* ELEC. SERVICE NOT FOUND. EQUIPMENT GATE LOCKED
03/16/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935* NO WORK PROGRESS A REFEE HAS BEEN ISSUED
03/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) CLEAN SURFACE BEHIND GROUND LUG SEC 250-12 2) HAS NOT BEEN CORRECTED AND IS TYPE OF SCREW USED FOR THUADED ENTRY. (CRICKET DISCONNECT SW) BY TELCO CABINET SINCE THERE WERE NO PLANS ON SITE, COULD NOT TELL WHERE GUTTER WAS OR HOW TO GET TO IT. ALSO SINCE THERE ARE TWO SERVICES ON THIS BLDG IN CLOSE PROXIMITY TO EACH OTHER, THE 1999 NEC REQUIRES THEIR GROUNDING SYSTEM TO BE TOGETHER. SEC 250-58 A COMMON GROUNDING ELECTRODE SYSTEM
02/06/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) WORKING CLEARANCES IN FRONT OF DISCONNECT. 2) CLEAN SURFACE BEHIND GROUND LUG 250-12 3) CANNOT USE SHEET METAL SCREWS 250-8 4) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD 5) LOOSE FITTINGS AT PULL GUTTER 6) NEED PERMANENT ADDRESS LABELS (NO INK) 7) NEED TO SEE AFTER CROSS OVER OK TO CLEAR POWER