Permit: T00CM05283

Parcel: 13316030E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/29/2001 ELECTRIC - FINAL Approved
08/27/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/23/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTE 1.) SUPPORT MC CABLE WITHIN 12" EACH TERMINATION PER N.E.C. 2.) CLOSE COVER TO J-BOX ON LT FIXTURE 3.)HAVE ELECTRICAL CONTR. ON SITE NEXT INSPECTION, NEED TO CHECK CONNECTIONS IN X-FORM, BONDING, ETC. ALSO CHECK INSIDE NEW BREAKER PANEL. 4.) UPDATE OR INSTALL PANEL SCHEDULE.