Permit: T00CM05269

Parcel: 125100350

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/03/2001 FRAMING Approved IVRS - Inspection 0000*
12/29/2000 FRAMING Denied IVRS - Inspection 0999*/1. BATH DRAIN NOT CONNECTED. 2. W/C FLOOR FLANGE NOT IN. 3. WALL HEATERS MUST EACH BE ON SEPARATE 20 AMP CIRCUITS WIRED WITH #12 WIRE. 4. LAUNDRY ROOM DOOR IN BEARING WALL MUST HAVE A DOUBLE 2 X 4 HEADER WITH 2 X 4" IN VERTICAL NOT FLAT.