Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05255
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*RE LEE TO SUBMIT LETTER STATING DISC. SWITCH FOR SWEEPER ON COOLING TOWER MTD. BY MANUFACTURER PER LISTING AND DESIGN OF TOWER. FAX 791-3205 ATTEN: RAY M. OR DAN SANTA CRUZ. | |
02/28/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) DISCONNECT FOR SWEEPER IN VIOLATION OF DEDICATED WORKING SPACE. SHOULD HAVE 30" HORIZONTAL 42" IN FRONT DUE TO METALIC WALL OPPOSITE DISCONNECT 110-26 N.E.C. 2.) DBL LUGGING IN EXISTING PANEL NOT ALLOWED 110-3 N.E.C. | |
02/27/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* COULD NOT SCHED W/CONTR. TO RESCHEDULE WITH MECH INSP FOR THRU 2-28-02. |