Permit: T00CM05255

Parcel: 12112404E


Addresses:

1635 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05255

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*RE LEE TO SUBMIT LETTER STATING DISC. SWITCH FOR SWEEPER ON COOLING TOWER MTD. BY MANUFACTURER PER LISTING AND DESIGN OF TOWER. FAX 791-3205 ATTEN: RAY M. OR DAN SANTA CRUZ.
02/28/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) DISCONNECT FOR SWEEPER IN VIOLATION OF DEDICATED WORKING SPACE. SHOULD HAVE 30" HORIZONTAL 42" IN FRONT DUE TO METALIC WALL OPPOSITE DISCONNECT 110-26 N.E.C. 2.) DBL LUGGING IN EXISTING PANEL NOT ALLOWED 110-3 N.E.C.
02/27/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000* COULD NOT SCHED W/CONTR. TO RESCHEDULE WITH MECH INSP FOR THRU 2-28-02.