Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*RE LEE TO SUBMIT LETTER STATING DISC. SWITCH FOR SWEEPER ON COOLING TOWER MTD. BY MANUFACTURER PER LISTING AND DESIGN OF TOWER. FAX 791-3205 ATTEN: RAY M. OR DAN SANTA CRUZ. |
| 02/28/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) DISCONNECT FOR SWEEPER IN VIOLATION OF DEDICATED WORKING SPACE. SHOULD HAVE 30" HORIZONTAL 42" IN FRONT DUE TO METALIC WALL OPPOSITE DISCONNECT 110-26 N.E.C. 2.) DBL LUGGING IN EXISTING PANEL NOT ALLOWED 110-3 N.E.C. |
| 02/27/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* COULD NOT SCHED W/CONTR. TO RESCHEDULE WITH MECH INSP FOR THRU 2-28-02. |