Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05253
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
03/28/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1. PLEASE IDENTIFY GROUNDING CONDUCTOR AND BOND ENCLOSURE AT VFDS 2.) WE HAVE EXPOSED #12 CONDUCTORS PLEASE PUT IN A BOX 3.) FINISH GAS BOND OK ROOF. OK TO CLEAR. | |
03/24/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) RISER HEIGHT TO BE 18' PER CODE 230-24(B). 2.) SPLIT BOLT IS LISTED FOR ONLY A RUN AND TAP 2 WIRES. 3.) GROUNDING ELECTRODE ENCLOUSER/RACEWAY TO BE BONDED BOTH ENDS 4.) STRAP CONDUITS WITH IN 3' OF GUTTER AND AS 250-64(E) PER CODES.5.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED CONDUCTOR 250-24. 6.) MAIN BONDING JUMPERS TO BE SIZED PER 250-102, 250-66,250-122. 7.) PLEASE VERIFY FAULT CURRENT AS ON PLAN #2 ALSO WHAT IS FAULT CURRENT RATING FOR 200 AMP MAIN. 8.) BOND ALL BOND BUSHINGS AND TERMANATE ALL STRANDS 9.) PERMANENT METAL ADDRESS LABELS ARE REQUIRED FOR EACH METER. 10.) PLEASE VERIFY INTERIOR SIDE OF WATER BOND. 11.) A GAS BOND IS REQUIRED 250-104. 12.) PLEASE VERIFY GROUND RODS. |