Permit: T00CM05253

Parcel: 115180220


Addresses:

1501 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05253

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/28/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. PLEASE IDENTIFY GROUNDING CONDUCTOR AND BOND ENCLOSURE AT VFDS 2.) WE HAVE EXPOSED #12 CONDUCTORS PLEASE PUT IN A BOX 3.) FINISH GAS BOND OK ROOF. OK TO CLEAR.
03/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1.) RISER HEIGHT TO BE 18' PER CODE 230-24(B). 2.) SPLIT BOLT IS LISTED FOR ONLY A RUN AND TAP 2 WIRES. 3.) GROUNDING ELECTRODE ENCLOUSER/RACEWAY TO BE BONDED BOTH ENDS 4.) STRAP CONDUITS WITH IN 3' OF GUTTER AND AS 250-64(E) PER CODES.5.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED CONDUCTOR 250-24. 6.) MAIN BONDING JUMPERS TO BE SIZED PER 250-102, 250-66,250-122. 7.) PLEASE VERIFY FAULT CURRENT AS ON PLAN #2 ALSO WHAT IS FAULT CURRENT RATING FOR 200 AMP MAIN. 8.) BOND ALL BOND BUSHINGS AND TERMANATE ALL STRANDS 9.) PERMANENT METAL ADDRESS LABELS ARE REQUIRED FOR EACH METER. 10.) PLEASE VERIFY INTERIOR SIDE OF WATER BOND. 11.) A GAS BOND IS REQUIRED 250-104. 12.) PLEASE VERIFY GROUND RODS.