Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T00CM05213
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2001 | MECHANICAL - HOODS | Approved | IVRS - Inspection 0000* | |
| 09/11/2001 | MECHANICAL - HOODS | Denied | IVRS - Inspection 0999*GREASE DUCT NOT ADEQUATELY WELDED PROVIDE GREASE DUCT WRAP AT COLLAR ON HOOD. COVER ALL EXPOSED WOOD WITHIN 18" OF TOP OF HOOD. | |
| 08/30/2001 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*OK TO LIFT HOODS INTO POSITION 1ST WRAP FLAME CHECK, OK OK TO SET DUCT W/1ST WRAP INTO POSITION. 1BR RATED CHASES OK. |