Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2001 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
IVRS - Inspection 0000*1.) WATER SERVICE FROM MAIN TAP TO BLDG. SERVICE IS OK 2.) OK TO BACKFILL TRENCH. 3.) NOTE: BACKFLOW PREVENTER HAS NOTE BEEN INSTALLED @ THIS TIME. |
| 08/21/2001 |
PLUMBING - YARD WTR LINE/TEST |
|
Denied |
IVRS - Inspection 0999*1.) 2" WATER SERVICE HAS LEAK 2.) 2" SOFT COPPER HAS KINKS IN LINE MUST REPLACE WITH NO KINKS. |
| 08/17/2001 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION. |