Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T00CM05213
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* OK TO BACKFILL | |
| 04/30/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 4" BACK PITCH ON SEWER INTO INTERCEPTOR | |
| 04/26/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1) BACK PITCH ON 4" ABS TO INTERCEPTOR 2) REQUIRED 2" VENT MAY ONLY BE RAN 1/3 THE DEVELOPED LENGTH (12) IN THE HORIZONTAL POSITION (40') VENT EXCEEDS 40' | |
| 04/23/2001 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* | |
| 04/20/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1) MUST PROVIDE FULL WATER TEST ON WASTE AND VENT SYSTEM. LOTS OF AIR IN LINES. 2) BLDG SEWER TRENCH HAS ENCROCHED 45 DEGREES RULE OF BEARING FOOTER. SEE SEC. 313.3 94 UPC 3) HORIZONTAL VENT FOR CAN WASH DRAIN MUST BE 6" ABOVE FLOOD RIM LEVEL SEE SEC. 905.3 94 UPC 4) 2" FLOOR SINKS AND DRAINS HAVE EXCEEDED 5'-0" MAX DISTANCE FOR TRAP ARMS. SEE TABLE 10-1 94 UPC 5) WILL REQUIRE A LETTER FROM ARCHITECT STATING HE WILL ACCEPT ABS SCH 40 INLIEU OF CAST IRON 6) WILL REQUIRE COMPRESSION TEST ON BLDG SEWER TRENCH WHERE ENCROCHMENT OF 45 DEGREES RULE ALONG WEST SIDE OF BLDG |
|
| 04/19/2001 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* 1) 4" WASTE LINE THAT SHARES COMMON TRENCH IN BLDG OK |