Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 12/20/2000 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 12/18/2000 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/1. ELECTRIC SERVICE RISER NOT PROPERLY BONDED. LAST SENTENCE OF NEC. SECTION 250-94. I SUGGEST YOU USE AN APPROVED BONDING RING/BUSHING. 2. YOUR UFER GROUND WAS NOT INSPECTED BY C.O.T. YOU MUST INSTALL 2 EACH 8FT GROUND RODS A MINIMUM OF 6 FEET APART CONNECTED TO ELECTRIC SERVICE WITH A CONTINUOUS #4 GROUND CONDUCTOR. |