Permit: T00CM05204

Parcel: 124141120


Addresses:

1320 E 16TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/04/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/28/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) NOTES: OK WALLS AND CEILINGS, EXCEPT WHERE CABLES ENTER CONDUIT SLEEVES AT EAST END OUTSIDE WALLS, CABLE JACKET DAMAGED, REPAIR OR REPLACE ROMEX AT THESE LOCATIONS
04/22/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT SE CABLE FEEDER AT 4½' INTERVALS AND WITHIN 12" AT TERMINATIONS. 2) USE CONNECTORS TO SECURE ROMEX ON ALL STEEL BOXES, EXH. FANS. ROMEX CONNECTORS TO BE INSTALLED PER LISTING IN PANELS, DO NOT USE OVERSIZED CONNECTORS FOR MULTIPLE CABLE TERMINATIONS INTO PANELS. 3) STEEL CONDUIT SLEEVES MUST HAVE BUSHED CONNECTORS AT EACH END TO PROTECT CABLE FROM ABRASION. 4) FEEDER CABLE OUTER JACKET MUST ENTER INTO SERVICE ENCLOSURE BY AT LEAST ¼". 5) RE-ROUTE ROMEX CABLE BEHIND GAS LINES (PINCHED)