Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) NOTES: OK WALLS AND CEILINGS, EXCEPT WHERE CABLES ENTER CONDUIT SLEEVES AT EAST END OUTSIDE WALLS, CABLE JACKET DAMAGED, REPAIR OR REPLACE ROMEX AT THESE LOCATIONS | |
| 04/22/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT SE CABLE FEEDER AT 4½' INTERVALS AND WITHIN 12" AT TERMINATIONS. 2) USE CONNECTORS TO SECURE ROMEX ON ALL STEEL BOXES, EXH. FANS. ROMEX CONNECTORS TO BE INSTALLED PER LISTING IN PANELS, DO NOT USE OVERSIZED CONNECTORS FOR MULTIPLE CABLE TERMINATIONS INTO PANELS. 3) STEEL CONDUIT SLEEVES MUST HAVE BUSHED CONNECTORS AT EACH END TO PROTECT CABLE FROM ABRASION. 4) FEEDER CABLE OUTER JACKET MUST ENTER INTO SERVICE ENCLOSURE BY AT LEAST ¼". 5) RE-ROUTE ROMEX CABLE BEHIND GAS LINES (PINCHED) |