Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00CM05198
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) ALL CORRECTION MADE OK 2.) PLUMBING FINAL OK 3.) OK FOR C OF O PENDING VERFICIATION OF CERTICICATION ON INTERIOR BACKFLOW DEVICE 1/2" WATTS 009 QT140854 | |
07/19/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) ICE MAKER IN WAITING ROOM REQUIRES BACKFLOW PROTECTION 2.) PLAN INDICATES THAT ICE MAKER WASTES INDIRECTLY INTO FLOOR SINK #1 WHICH ISNT THERE 3.) DO NOT INSTALL ICEMAKER UNTIL THESE CORRECTION ARE MADE. | |
07/17/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) ALL SINKS REGUIRE CLEAN OUTS 2.) HANDICAPPED RESTROOM #109 HAS A VARITY. PLEASE PROVIDE DOCUMENTATION ALLOWING NO WHEEL CHAIR ACCESS TO THE LAVATORY 3.) ICE MAKER IN LOBBY REGUIRES BACK FLOW PROTECTION 4.) PROVIDE LETTER FROM ARCHETECT SUPERCEDING GENERAL NOTE #4 OFFSETS ON SINKS. | |
06/07/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1)PLEASE REVIEW REQUIREMENTS FOR INDIRECT WASTE PIPING AND INSTALL PER CODE.2)EXPANSION TANK NEEDS TO BE SUPPORTED.3)PLEASE READ GENERAL NOTE #4 P-1.4)ALL SINKS REQUIRE CLEAN-OUTS.5)PLEASE READ GENERAL NOTE #18 P-L. |