Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM05179
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
05/20/2002 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
05/16/2002 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*TEST OK AT THIS TIME 1ST FLOOR ONLY CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST PLEASE PROVIDE APPROVED REVISED PLAN AT TIME OF NEXT INSP. CALL WHEN READY FOR 2ND FLOOR NOTE FIXTURE ADDED NEED FEC' FROM WASTE WATER. | |
05/15/2002 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*PROVIDE CO END OF RUN. | |
05/13/2002 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* NO PLAN NO INSPECTION NO TEST DO NOT COVER. | |
05/10/2002 | PLUMBING - INTERMEDIATE | Denied | 1.) MUST USE L SWEEPS ON WASTE VERTICAL TO HORIZONTAL DRAINAGE. 2.) MUST HAVE MAX 1 1/2" STUBB OUT FOR LAVATORY WASTE. 3.) OK TO DRYWALL ON SIDE OF PLBG. WALLS ONLY. 4.) RE TEST SYSTEM. | |
05/08/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* CAN NOT MAKE A DRAIN DISCHARGE INTO A VENT WET VENT IS FOR VERTICAL DRAINAGE ONLY FOR LAVATORYS. 2.) MUST PROVIDE WATER TEST ALL THE WAY TO ROOF ON WASTE & VENT SYSTEM. 3.) CAN NOT HAVE 2" TRAP ARMS FOR DRINKING FOUNTAIN. THIS MUST BE 1 1/2 ALLTHE WAY TO BARREL. |