Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM05179
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
07/01/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0950*1.) NEED PANELS, DISCONNECTS, AND ANY DISCONNECTS ON ROOF A/C UNITS LABELED 2.) NEED GROUNDING BUSHING ON 4" EMT AT MAIN SERVICE CABINETS. | |
05/17/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) ROUGH IN OF WALLS IN BATHROOM AND BACK STORAGE AREA. | |
05/15/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0925*DENIED NO APPROVED PLANS ON SITE. | |
05/08/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1.) SIX 1" EMT CONDUITS FOR A/C UNITS ON ROOF.. | |
04/29/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
04/29/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) CENTER DIVIDING WALL ROUGH IN OK 2.) ELECTRIC PANELS INSPECTED. PLAN MUST BE REVISED TO REFLECT THE "AS BUILT" CONFIGURATION DO THIS ASAP. |