Permit: T00CM05171

Parcel: 117030970


Addresses:

20 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
09/13/2001 ELECTRIC - UFER Approved IVRS - Inspection 0000*
08/13/2001 ELECTRIC - UFER Denied IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF PROPER GROUND SYSTEM, EXPOSE OR INSTALL 2 GROUND RODS AT LEAST 6' APART CONNECTED TO SERVICE PANEL WITH #4 COPPER CONDUCTOR 2) PROVIDE PROOF THAT MAINTENCE CIRCUIT IS GFCI PROTECTED 3) NO ACCESS TO HOUSE 4) NO ADDRESS ON PROPERTY-3" HIGH NUMBERS VISABLE FROM STREET