Permit: T00CM05166

Parcel: 10309074A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05166

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/26/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
12/19/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE PROVIDE LETTER VERIFING TORQUE VALUES.
12/05/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/04/2001 ELECTRIC - FINAL Partial Approval 1.) IDENDIFYG GROUNDING CONDUCTOR AT TERMANAL. 2.) USE FUSES AS PER PLAN 3.) INSTALL ACORN GROUND CLAMP AS PER MANUFACTURE. 4.) PROVIDE LETTER VERIFYING TORQUE VALVES 5.) PROVIDE WORKING CLEARENCE INFRONT OF SERVICE 110-26. 6.) VERIFY WATER BOND AS PER PLANS.
11/14/2001 ELECTRIC - FINAL Denied