Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/23/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 04/27/2001 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ UDNERSLAB PORTION OF DWV HAS PREVIOUSLY BEEN INSPECTED, OK TO POUR ? FLOOR, DRAINAGE CONNECTION TO MAIN AND BLD CLEANOUTS HAVE NOT BEEN INSPECTED |
| 03/29/2001 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ALL UNDER SLAB DWV INSTALLED BUT FOR CLEAN OUTS AND PORTABLE WASHER. |
| 03/27/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. NO PLAN ON SITE. 2. DRAIN LINE DOES NOT APPEAR TO EXTEND A MINIMUM OF 2 FEET BEYOND EXTERIOR WALL. 3. NO CLEAN OUTS INSTALLED. 4. PROVIDE UPSTREAM MAN HOLE AND FINISHED FLOOR ELEVATIONS. |
| 03/26/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. USE SCREEDED FILL UNDER AND AROUND 3" SEWER LINE. 2. VERIFY UPSTREAM MAN HOLE AND FINISH FLOOR ELEVATION. |