Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM05135

Parcel: 125031310

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/31/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/04/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
08/23/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) PROTECT WIRES IN METAL BOXES 2.) ELETRIC OUTLETS REQUIRED WITHIN 6" OF DOORS & 12" THEREAFTER 3.) PROVIDE PROOF OF SPECIAL INSPECTION 4.) VARITY STAIR HEAD RISER. 5.) ELECTRIC NOT ALLOWED IN PLENIUM 6.) CONDENATE NOT PROPERLY TERMINATED 7.) HOLES IN STEEL STUDS EXCEED 1 1/2 X 4 1/2 PROVIDE ENGINEERING APPROVED REPAIR. 8.) WALL TRACKS NOT PROPERLY ANCHORED. REINFORCE WITH STUD 9.) BOND/AROUND WIRE IN CONTACT WITH DISSIMILAR METAL. 10.) SHOWER NOT PROPERLY VENTE 11.) LPI AT GARAGE REQ HANGER 12.) ROOF JOISTS MISSING SCREWS. 13.) 2ND FLOOR SHGAR WALL STUDS CUT
08/21/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*