Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM05112
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 12/20/2000 | FRAMING | Denied | IVRS - Inspection 0999*/1. FHA 16 GA STRAP OVER BORED DBL TOP PLATES 2 LOCATIONS. 2. INSTALL CONDENSATION LINES FOR FURNACE. 3. CLIP BOTH SIDES OF GIRDER AT GARAGE 4. DRAFT STOP NEED TO BE 1" THICK AT CAVITYS. 5. SECURE EXHAUST FAN VENT TO TOP CORD OF TRUSS. 6. PROVIDE ANCHOR BOLTS WITHIN 12 INCHES OF PANEL ENDS. 7. SEAL SOLE PLATE SPLICES FROM INFILTRATIONS. 8. BATHROOM 20 AMP BRANCH CIRCUIT CAN ONLY SERVE RECEPS FOR BATHROOMS SEE SEC. 210.11 C. 3. 9. SECURE GAS LINES PER UPC TABLE 12-2 MUST BE APPROVED CLAMP NO PLUMBERS TAPE. |