Permit: T00CM05112

Parcel: 103181960

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM05112

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2001 FRAMING Approved IVRS - Inspection 0000*
12/20/2000 FRAMING Denied IVRS - Inspection 0999*/1. FHA 16 GA STRAP OVER BORED DBL TOP PLATES 2 LOCATIONS. 2. INSTALL CONDENSATION LINES FOR FURNACE. 3. CLIP BOTH SIDES OF GIRDER AT GARAGE 4. DRAFT STOP NEED TO BE 1" THICK AT CAVITYS. 5. SECURE EXHAUST FAN VENT TO TOP CORD OF TRUSS. 6. PROVIDE ANCHOR BOLTS WITHIN 12 INCHES OF PANEL ENDS. 7. SEAL SOLE PLATE SPLICES FROM INFILTRATIONS. 8. BATHROOM 20 AMP BRANCH CIRCUIT CAN ONLY SERVE RECEPS FOR BATHROOMS SEE SEC. 210.11 C. 3. 9. SECURE GAS LINES PER UPC TABLE 12-2 MUST BE APPROVED CLAMP NO PLUMBERS TAPE.