Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE A SUN SHIELD OVER CANVAS CONNECTORS. 2.) BLOCK & CLAMP GAS PIPING & CONDENSATE DRAIN. 3. PANINT EXPOSED PVC W/LATEX PAINT. 4.) CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. MUST GO TO THE GROUND. 5.) PROVIDE AN OUTSIDE AIR VENT ON AC UNIT. 6.) PROVIDE A PRESSURE TEST ON GAS SYSTEM. CALL FOR PLUMBING INSPECTION. RECALL FOR MECHANCIAL FINAL. |