Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 11/29/2000 | ELECTRIC - INTERMEDIATE | Denied | COMPLETE SUPPORTS FOR ROMEX FHA STRAPS REQUIRED WHERE CABLE IS LESS 1 1/4" FROM SURFACE OF STUDS. INSTALL BUSHED ENDS WHERE ROMEX EXITS/ENTERS CONDUIT 300-6 NEC |