Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/12/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/09/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. WATER HEATER VENT WITHIN 8 FT OF VERT WALL MUST EXTEND 2 FEET ABOVE VERT WALL. 2. ROOF A.C. GAS NOT CONNECTED. 3. WASTE VENT CANNOT BE DRILLED FOR A/C CONDENSATE. 4. PAINT ALL ROOF TOP ABS AND PVC PLASTIC PIPES. 5. W/H "B" VENT PLUGGED WITH TAPE. 6. WH VENT CONNECTOR REQUIRES 3 SCREWS. 7. SMOKE DETECTOR REQUIRED IN M/BR DUE TO 2 FT CEILING HEIGHTS CHANGE. 8. INSULATION AND STUCCO INSULATION CERTIFICATES REQUIRED. |