Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 10/11/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* GAS SHUT OFF VALVE MUST BE WITHIN 3' OF EQUIPMENT # 8 WIRE IS TOO SMALL FOR 60 AMP SERVICE USE #6 WIRE OR CHANGE FUSES TO 50 DAMP |