Date Description Inspector Results Comments
10/30/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
ALL CORRECTIONS HAVE BEEN MADE
10/11/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
GAS SHUT OFF VALVE MUST BE WITHIN 3' OF EQUIPMENT
# 8 WIRE IS TOO SMALL FOR 60 AMP SERVICE
USE #6 WIRE OR CHANGE FUSES TO 50 DAMP