Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/30/2000 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/11/2000 |
ELECTRIC - FINAL |
|
Denied |
A FUSED DISCONNECT MUST BE INSTALLED, AT OR NEAR THE BUSS GUTTER, TO PROTECT THE CONDUCTORS WHICH SUPPLY POWER TO THE A/C UNIT RECALL INSPECTION WHEN CORRECTIONS IS COMPLETE |