Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05008
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* NO ONE ON SITE | |
01/29/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* CANNOT STACK LUGS DISCONNECTS WITH LABEL STAND BY SYSTEM PER CODE 708-2 BOND DEVICE NEEDED LINE SIDE OF GENERATOR TO TRANSFER SWITCH 250-94 SECURE 1/2 CONDUIT AT GENERATOR CHECK BONDING OF JUNCTION BOX 250-96 CONDUIT IN UPSTAIR ELECTRIC ROOM EXTREMLY WARM. 6 SWITCH RUN THROUGH TO PANEL |