Permit: T00CM05008

Parcel: 103090670

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* NO ONE ON SITE
01/29/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
CANNOT STACK LUGS DISCONNECTS WITH
LABEL STAND BY SYSTEM PER CODE 708-2
BOND DEVICE NEEDED LINE SIDE OF GENERATOR TO TRANSFER SWITCH 250-94
SECURE 1/2 CONDUIT AT GENERATOR
CHECK BONDING OF JUNCTION BOX 250-96
CONDUIT IN UPSTAIR ELECTRIC ROOM EXTREMLY WARM. 6 SWITCH RUN THROUGH TO PANEL