Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
| 06/20/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) LOOSE SEAL TIGHT FITTINGS 2) CANNOT USE SHEET METAL SCREW FOR GROUNDING 250-8 | |
| 05/22/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210*1)PLEASE IDENTIFY THE SERVICE SWITCHES NEXT TO C.T. CAN.USE PERM.LABEL.2)INDENTIFY SWITCH AT A/C UNIT. USE PERMANENT LABEL-NO "MAGIC MARKER". 3)INDENTIFY FAR END SWITCHES WITH I.D. OF POWER SOURCE-NOT NAME OF A/C UNIT SERVED. | |
| 05/03/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) BOND GUTTER 250-96 2) NEED TO SEE AFTER CROSS OVER |