Permit: T00CM04989

Parcel: 11445262J

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
02/14/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
01/23/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*DUCT SMOKE DETECTORS MUST BE UPSTREAM FROM ALL SUPPLY DUCTS. RELOCATE AS NEEDED & RECALL FOR INSPECTED. PROVIDE CONDENSATE DRAIN TO HP-1 AS PER PLAN.