Permit: T00CM04989

Parcel: 11445262J

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM04989

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
02/14/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*NO COMPIANCE WITH #1. SEE NOTES.
01/23/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*NOTES SPACE G-1 & G-2 1.) SUPPORT FLEX WITHIN 12" OF BOXES AND SUPPORT BOXES MTD ON GRID FROM STRUCTURE. 2.) INSTALL BOND BUSHINGS BOTH ENDS OF METAL CONDUIT USED FOR GROUND CONDUCTOR TO PANELS. 3.) COMPLETE MAKE UP OF J-BOX IN FRONT BY DOOR. 4.)2" CONDUIT STUB-UPS FOR SPACE PANELS WHERE BROKEN OFF DURING CONST. BELOW SLAB. NEED TO INSPECT REPAIR WORK.
09/13/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK WEST SOFFITS CAN LIGHTS.