Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM04989
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
02/14/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*NO COMPIANCE WITH #1. SEE NOTES. | |
01/23/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*NOTES SPACE G-1 & G-2 1.) SUPPORT FLEX WITHIN 12" OF BOXES AND SUPPORT BOXES MTD ON GRID FROM STRUCTURE. 2.) INSTALL BOND BUSHINGS BOTH ENDS OF METAL CONDUIT USED FOR GROUND CONDUCTOR TO PANELS. 3.) COMPLETE MAKE UP OF J-BOX IN FRONT BY DOOR. 4.)2" CONDUIT STUB-UPS FOR SPACE PANELS WHERE BROKEN OFF DURING CONST. BELOW SLAB. NEED TO INSPECT REPAIR WORK. | |
09/13/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK WEST SOFFITS CAN LIGHTS. |