Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T00CM04989
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2001 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000*2" EMT RISER EXTENTION CONCRETE TO PANEL. | |
09/11/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*NOTES 1.) OK SECONDARY FEEDERS U.G. 2.) NEED TO SEE METHOD USED TO REPAIR 2" PANEL FEEDER BELOW INTERIOR SLAB. | |
09/06/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0245*NOTES 1.) BURIAL DEPTH NEEDS TO BE 24" PER 300-5 NEC. 2.) LOOSE FITTINGS 3.) 2" FEEDER CONDUITS NOT MECHANICALLY CONTINUIOUS BELOW SLAB. | |
09/04/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0935*A RE-INSPECTION FEE IS ASSESED, PLEASE RAY RE-FEE 201 N STONE PRIOR TO FUTURE INSP. | |
08/29/2001 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000*CANCELLED. | |
08/28/2001 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
06/08/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
06/05/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*1)OK U.G. FEEDERS.2)OK BRANCH WIRING SOUTH SOFFITS. | |
06/01/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*PHONE CONDUITS ONLY-OK |