Permit: T00CM04989

Parcel: 11445262J

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
09/17/2001 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*2" EMT RISER EXTENTION CONCRETE TO PANEL.
09/11/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*NOTES 1.) OK SECONDARY FEEDERS U.G. 2.) NEED TO SEE METHOD USED TO REPAIR 2" PANEL FEEDER BELOW INTERIOR SLAB.
09/06/2001 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0245*NOTES 1.) BURIAL DEPTH NEEDS TO BE 24" PER 300-5 NEC. 2.) LOOSE FITTINGS 3.) 2" FEEDER CONDUITS NOT MECHANICALLY CONTINUIOUS BELOW SLAB.
09/04/2001 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0935*A RE-INSPECTION FEE IS ASSESED, PLEASE RAY RE-FEE 201 N STONE PRIOR TO FUTURE INSP.
08/29/2001 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*CANCELLED.
08/28/2001 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*
06/08/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
06/05/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*1)OK U.G. FEEDERS.2)OK BRANCH WIRING SOUTH SOFFITS.
06/01/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*PHONE CONDUITS ONLY-OK