Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/09/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/03/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 05/08/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST NOT READY-NEED MINIMUM 10 PST ON GUAGE AT TIME OF INSPECTION 2) SJ FLEX CABLE NOT ALLWED INSIDE OF WALL 3) FIRE STOP DROP CEILING AT CLOSET AND MECH ROOM 4) GROUND ALL METAL ELECTRIC BOXES 5) BATHROOM MUST BE ON A DEDICATED 20 AMP CIRCUIT WITH 12 GUAGE WIRE 6) FAN SUPPORT CANNOT USE DRY WALL SCREWS USE MINIMUM 4 EACH #12 X 1" WOOD SCREWS 7) WATER HEATER REQUIRES COMBUSTION AIR |