Permit: T00CM04980

Parcel: 113021940


Addresses:

1031 E KING ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/09/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
05/08/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST NOT READY-NEED MINIMUM 10 PST ON GUAGE AT TIME OF INSPECTION 2) SJ FLEX CABLE NOT ALLWED INSIDE OF WALL 3) FIRE STOP DROP CEILING AT CLOSET AND MECH ROOM 4) GROUND ALL METAL ELECTRIC BOXES 5) BATHROOM MUST BE ON A DEDICATED 20 AMP CIRCUIT WITH 12 GUAGE WIRE 6) FAN SUPPORT CANNOT USE DRY WALL SCREWS USE MINIMUM 4 EACH #12 X 1" WOOD SCREWS 7) WATER HEATER REQUIRES COMBUSTION AIR