Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/24/2000 FRAMING Approved IVRS - Inspection 0000*
11/22/2000 FRAMING Partial Approval 3RD INTERMEDIATE INSPECTION SAME RESULTS. 1. PROVIDE NEC 370-17(C) PROTECT CABLE PER NEC 300-4 SECURE TO CENTER OF STUD. 2. FRAMING NOTES FROM PREVIOUS INSTP. 3. PROVIDE NEC 210-11 (C) (3) NOTE A REINSPECTION FEE IS REQUIRED PRIOR TO CALLING IN THIS INSPECTION.
11/21/2000 FRAMING Partial Approval 1. PROVIDE 60 PSI TO PEX LINES. 2. PVC SAGS FOR CONDENSATE LINES 3. SHEARWALL #2 NOT COMPLETE 4. ROMEX SECURED ON EDGE MORE NOT ALLOWED 2 OR MORE WIRE 3.
11/20/2000 FRAMING Denied 1. LOOSE ANCHOR BOLTS THRU OUT PROVIDE WITHIN 12"S OF SPLICE 2. DETAIL 17/SD3 NOT COMPLETE. 3. COMBUSTIBLE MATERIAL WITHIN 1 INCH OF FLUE PIPE. 4. LOW VOLT LINE CANNOT BE INSTALLED IN HIGH VOLT IN ATTIC. 5. PROVIDE RECEPTACLE OUTLET IN ATTIC. 6. WIRE NOT COMPLETE AT EXHAUST FANS 7. CONDENSATION LINES SAGGING. 8. SHEARWALL #2 MISSING BLOCKS BETWEEN LADDER.