Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/22/2000 |
FRAMING |
|
Partial Approval |
3RD INTERMEDIATE INSPECTION SAME RESULTS. 1. PROVIDE NEC 370-17(C) PROTECT CABLE PER NEC 300-4 SECURE TO CENTER OF STUD. 2. FRAMING NOTES FROM PREVIOUS INSTP. 3. PROVIDE NEC 210-11 (C) (3) NOTE A REINSPECTION FEE IS REQUIRED PRIOR TO CALLING IN THIS INSPECTION. |
| 11/21/2000 |
FRAMING |
|
Partial Approval |
1. PROVIDE 60 PSI TO PEX LINES. 2. PVC SAGS FOR CONDENSATE LINES 3. SHEARWALL #2 NOT COMPLETE 4. ROMEX SECURED ON EDGE MORE NOT ALLOWED 2 OR MORE WIRE 3. |
| 11/20/2000 |
FRAMING |
|
Denied |
1. LOOSE ANCHOR BOLTS THRU OUT PROVIDE WITHIN 12"S OF SPLICE 2. DETAIL 17/SD3 NOT COMPLETE. 3. COMBUSTIBLE MATERIAL WITHIN 1 INCH OF FLUE PIPE. 4. LOW VOLT LINE CANNOT BE INSTALLED IN HIGH VOLT IN ATTIC. 5. PROVIDE RECEPTACLE OUTLET IN ATTIC. 6. WIRE NOT COMPLETE AT EXHAUST FANS 7. CONDENSATION LINES SAGGING. 8. SHEARWALL #2 MISSING BLOCKS BETWEEN LADDER. |