Permit: T00CM04968

Parcel: 128100780


Addresses:

5421 E WILLIAMS BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T00CM04968

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2001 PLUMBING - FINAL Approved 1)ALL CORRECTIONS FROM 3/16/2001 MADE OK.2)PLUMBING FINAL FOR 1ST AND 2ND FLOOR OK.3)OK FOR C OF O PENDING ANY OTHER INSPECTIONS.
05/16/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* SECOND FLOOR: 1) EXTEND GREASE TRAP TO GRADE 2) DIRECT RAIN LEADERS (OVERFLOW) AWAY FROM GREASE TRAP 3) EXPANSION TANK NEEDS SUPPORT 4) NEED TO SEE LISTING FOR ADA LAVATORY FAUCET 5) NO INSTALLATION KITS ON LAV (ADA) 6) 17" MAX ON ADA URINAL
01/03/2001 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*
OK FOR TEMP C OF O FIRST FLOOR ONLY BLDG HAS MINIMAL PLUMBING FACILITIES
COMPLETE FIRST FLOOR PLUMBING BEFORE 01-15-01
12/14/2000 PLUMBING - FINAL Partial Approval OK FOR TEMP C OF O PENDING ANY OTHER INSPECTIONS FOR FURNITURE MOVE IN ONLY