Permit: T00CM04937

Parcel: 13216600A


Addresses:

4004 S PARK AV


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T00CM04937

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
08/21/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*ACCEPT AS PER DAVE MANN BUILDING OFFICAL. BILL PARKS TRYING TO ORGANIZE MEETING BETWEEN SMOKE HAVE COPY OF APPROVAL BY DAVE MANN FOR NON RATED MATERIAL BEING IN A RETURN AIR PLENIUM.
03/02/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000* DISCUSSED RETURN PLENIUM AND REQUIREMENTS
02/08/2001 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*
AREA ALL DISPATCH AREA ABOVE GRID NOT ACCEPTABLE AS PLEMUM (RA)
SUPT'S OFFICE AREA ABOVE R.A. PLENIUM HAS EXPOSED COMBUSTIBLES