Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM04933
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
05/11/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) PROVIDE APPROVED DETAIL FRO SHEAR WALL 2) PROVIDE BLOCKING FOR NAILING TIP EDGE OF #3 SHEAR WALL AT BATHROOMS AND KITCHEN AND BEDROOM AND ENTRY 3) KITCHEN PENISULA NOT IN 4) MASTER BEDROOM TUB NOT IN FLOOR NOT BACK GROUNTED AT PENETRATIONS 5) MECH DUCTS AT FAMILY ROOM RESTRICTED TOO TIGHT OF BEND 6) REVISE PLAN FOR ALL FLEX DUCT | |
01/12/2001 | FRAMING | Denied | IVRS - Inspection 0999*/1. ITEMS 1, 4, 5 , 6 AND 8 FROM PRIOR INSPECTION NOT COMPLIED WITH. 2. PROVIDE APPROVED DETAIL FRO SHEAR WALL 3 CONNECTION TO ROOF. | |
12/22/2000 | FRAMING | Denied | IVRS - Inspection 0999*/1. PROVIDE BLOCKING FOR NAILING TOP EDGE OF #3 SHEAR WALL AT BATHROOMS AND KITCHEN AND BEDROOM AND ENTRY. 2. FIREBLOCK MISSING/BROKEN AT FAMILY ROOM. 3. SHEAR WALLS REQUIRE ANCHOR BOLTS NOT INSTALLED. 4. KITCHEN PENISULA NOT IN. 5. M/BATH TUB NOT IN FLOOR NOT BACK GROUTED AT PENETRATIONS. 6. MECH DUCTS AT FAMILY ROOM RESTRICTED TOO TIGHT OF BEND. 7. KIT AND DINING ROOM DUCTS NOT INSTALLED. 8. REVISE PLAN FOR ALL FLEX DUCT. | |
11/30/2000 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
11/28/2000 | FRAMING | Denied |