Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2000 | ELECTRIC - UFER | Approved | IVRS - Inspection 0000* | |
| 10/12/2000 | ELECTRIC - UFER | Denied | IVRS - Inspection 0920* 2 GROUND RODS REQUIRED PER PLAN CONDUITS BELOW OUTSIDE PANEL ARE COVERED METAL FRAME SHOULD BE BONDED SERVICE AREA AND DISCONNECT SWITCH LOCKED UNDERGROUND SPLICE BOX NEEDS TO BE OPENED FOR INSPECTION OF WIRING. SCHEDULE MEETING WITH MAINTENANCE PERSON OR CONTRACTOR 791-5550 #136 |