Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/30/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 11/28/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
1. COMPLETE BRACE PANELS PER UBC AT EAST WALL CHAP. 23 SEC. 232611.3. 2. PROVIDE VERT DEFLECTION FOR SCISSOR TRUSS PROVIDE APPROVED TRUSS CALC'S. 3. INSTALL DETAIL F. 4. INSTALL ANCHOR BOLTS WITHIN 12" OF SPLICES SOLE PLATE AND AT END OF BRACED WALLS. 5. GET REVISION STAMPED BY C.O.T. FOR ELIMINATION OF WINDOWS AT BATHROOM FOR FUTURE RECORD PURPOSES. 6. PROVIDE 1/8 INCH GAP AT ROOF SHEATHIN PER MANUF. SPEC'S ROOF NAILING OK. |