Permit: T00CM04896

Parcel: 125072770


Addresses:

2049 E 6TH ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T00CM04896

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
03/23/2001 EXT METAL CLIPS/EXT SHEATHING Denied 1. TRUSS BRACING NOT INSTALLED SEE TRUSS DRAWINGS. 2. TRUSSES REQUIRE BLOCKING AT TOP AND BOTTOM CHORDS PER UBC SECTIONS 2326.12.8. AN D2306.7. 3. ROOF SHEATHING REQUIRES SUPPORT AT EDGES UNDER PARAPET WALLS. 4. FRONT PORCH POST TO BEAM CONNECTION NOT MADE. 5. FRONT PORCH POST OF UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE. INSTALL SIMPSON UPB. 6 OR EQUAL. 6. PORCH RAFTERS NOT CLIPPED. 7. HOLD DOWNS MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS. MISSED AT NW. CORNER.
03/22/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0920*/NO PLANS OR PERMIT ON SITE.