Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T00CM04896
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2001 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
03/23/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1. TRUSS BRACING NOT INSTALLED SEE TRUSS DRAWINGS. 2. TRUSSES REQUIRE BLOCKING AT TOP AND BOTTOM CHORDS PER UBC SECTIONS 2326.12.8. AN D2306.7. 3. ROOF SHEATHING REQUIRES SUPPORT AT EDGES UNDER PARAPET WALLS. 4. FRONT PORCH POST TO BEAM CONNECTION NOT MADE. 5. FRONT PORCH POST OF UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE. INSTALL SIMPSON UPB. 6 OR EQUAL. 6. PORCH RAFTERS NOT CLIPPED. 7. HOLD DOWNS MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS. MISSED AT NW. CORNER. | |
03/22/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0920*/NO PLANS OR PERMIT ON SITE. |