Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2001 |
MECHANICAL - ABOVE CEILING |
|
Approved |
|
| 10/02/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
1) STABILIZE PHG. UNITS AND CONDENSOR SO NO SWAYING OCCURS DURING SERVICING OPERATIONS 2) HOW IS CONDENSOR DISCHARGE AIR GOING TO CLEARANCE AND NOT BE RE-CIRCULATED, CONSULT MANUFACTURERS SPECIFICATIONS 3) FURNACE POWER VENT ON WEST UNIT IS DISCHARGING INTO FRESH AIR INTAKE ON EAST UNIT |
| 08/30/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*SHOP AREA PARTIAL RENTAL OFFICE SUSPENDED ROUGH DUCT. AREA ABOVE CEILING TILES IS RETURN PLENIUM ALL MATERIAL MUST BE PLENIUM RATED. |