Permit: T00CM04888

Parcel: 11811013C


Addresses:

919 W SILVERLAKE RD

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
10/03/2001 ELECTRIC - TEMP POWER FOR TEST Approved OK TO CLEAR TEC.
10/01/2001 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection FOR TEMP POWER FOR MAIN SERVICE 1.) INSTALL GROUNDING BUSHING ON CONDUITS AHEAD OF OVER CURRENT PROTECT 99 NEC 250-94 2.) SCRAPE BEHING ALL GROUND LUGS ATTACHED TO EQUIPMENT 3.) UFER & NEUTRAL ISOLATED FROM EQUIPMENT ENCLOUSRE 4.) ADDRESS SERVICE PERMANENTLY 110-24 N.E.C 5.) TIE CT CAN TO GUTTER WITH SAME JUMPER AS #3.