Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM04888

Parcel: 11811013C


Addresses:

919 W SILVERLAKE RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
06/07/2001 ELECTRIC - UFER Approved IVRS - Inspection 0000*3/0 BARE CU. UFER TO:(A) 20'
+ OF REBAR.(B) 20' + OF 3/0 CU. WIRE IN FOOTING.
1" SPARE CONDUIT.SOUTH OF BUILDING TO VARIOUS IN GROUND J-BOXES.APPROVED (INCLUDED L.V. SECURITY).PROPANE AND UNLEADED CONDUITS FROM BUILDING TO FUEL ISLAND UNDERGROUND APPROVED.