| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2001 | ELECTRIC - UFER | Approved | IVRS - Inspection 0000*3/0 BARE CU. UFER TO:(A) 20' + OF REBAR.(B) 20' + OF 3/0 CU. WIRE IN FOOTING. 1" SPARE CONDUIT.SOUTH OF BUILDING TO VARIOUS IN GROUND J-BOXES.APPROVED (INCLUDED L.V. SECURITY).PROPANE AND UNLEADED CONDUITS FROM BUILDING TO FUEL ISLAND UNDERGROUND APPROVED. |